Damage to the rear waterwall of BKZ-420-140 NGM boiler caused by a pressure drop in the furnace

Author: Belyakov I.   Breus V.  

Publisher: Springer Publishing Company

ISSN: 1570-145X

Source: Power Technology and Engineering, Vol.47, Iss.1, 2013-05, pp. : 68-70

Disclaimer: Any content in publications that violate the sovereignty, the constitution or regulations of the PRC is not accepted or approved by CNPIEC.

Previous Menu Next

Abstract

An inspection of the tubes in the rear waterwall of the gas-and-oil-fired high-pressure drum boiler has revealed a deflection of 110 mm toward the furnace. It is proved that this damage is caused by a pressure drop in the boiler furnace during an emergency shutdown.