Fault Diagnosis in Transformer Based on Weighted Degree of Grey Slope Incidence of Optimized Entropy

Publisher: Edp Sciences

E-ISSN: 2261-236x|77|issue|01004-01004

ISSN: 2261-236x

Source: MATEC Web of conference, Vol.77, Iss.issue, 2016-10, pp. : 01004-01004

Access to resources Favorite

Disclaimer: Any content in publications that violate the sovereignty, the constitution or regulations of the PRC is not accepted or approved by CNPIEC.

Previous Menu Next

Abstract

Dissolved gas analysis (DGA) is an important method to find the hidden or incipient insulation faults of oil-immersed power transformer. However, code deficiency exists in the gas ratio methods specified by the IEC standard and complexity of fault diagnosis for power transformer. Hence a new model based on optimized weighted degree of grey slope incidence was put forward. Firstly, the entropy weight is used to determine objective weight of indices; then the model fault types are obtained by weighted degree of grey slope incidence. The combination of entropy weight with grey slope incidence analysis can fully utilize over all information of DGA and give full play to the superiority of grey slope incidence, which overcomes shortcomings of original grey slope incidence analysis. The experimental results also demonstrate that the improved method has higher accuracy compared with three-ratio method and general grey slope incidence analysis method. The diagnosis accuracy is 92.8%.