The fast and coordinated voltage control of distributed nodes inside a large scale wind farm is a stringent issue. To achieve the reactive power compensation without a dedicated upper communication system, this paper proposes a relative control strategy based on the local reactive power regulation. This method can realize the voltage coordination of the key equipment and feeder line nodes, on the basis of the relative voltage observations. Firstly, the stability analysis of a certain wind farm with pre-known parameters and structure is studied under the wind power fluctuations. Secondly, the optimal capacity configurations of the reactive power compensators are discussed, with multiple nodes inside the wind farms. Simulation results of a specific wind farm in North Hebei, China, validate the effectiveness of the proposed control, which is equipped with fast and stable voltage dynamic responses, as well as local reactive power compensations without remote communication.
Related content


Reactive power control of wind farms for voltage control applications
By Tapia A. Tapia G. Ostolaza J.X.
Renewable Energy, Vol. 29, Iss. 3, 2004-03 ,pp. :