Study on ventilation and noise reduction in the main transformer room in indoor substation

Publisher: Edp Sciences

E-ISSN: 2261-236x|44|issue|02058-02058

ISSN: 2261-236x

Source: MATEC Web of conference, Vol.44, Iss.issue, 2016-03, pp. : 02058-02058

Access to resources Favorite

Disclaimer: Any content in publications that violate the sovereignty, the constitution or regulations of the PRC is not accepted or approved by CNPIEC.

Previous Menu Next

Abstract

The noise emission should be considered in the ventilation and cooling design for the main transformer room of indoor substation. In this study, based on Soundplan software, effects of four common ventilation and cooling schemes on the cooling and sound insulation were compared. The research showed that the region with low noise requirement, the ventilation could be set on the outer wall or on the door of the main transformer room, while the region with high noise requirement, air inlet muffler or ventilation through the cable interlayer under the main transformer room must be used. All of the four kinds of ventilation schemes, ventilation through the cable interlayer is the best in cooling and noise reduction.